HZ-ICE includes an industrial DC UPS (with two 12V/5Ah sealed lead-acid batteries) that keeps the BACnet controller and alarm reporting active for approximately 7 hours after grid AC fails. The heating cables do not run on battery — there is not enough energy for that — but the panel’s intelligence stays active. The amber door pilot illuminates during battery operation. When grid power returns, the panel resumes normal operation automatically. The battery backup uses industrial-grade components rather than consumer UPS hardware, eliminating the replacement cycles associated with consumer battery backup products.

What is a welded contactor alarm?

Each HZ-ICE zone is switched by a definite-purpose contactor. A welded contactor is one that has failed in the closed (on) position — it continues passing current even when the panel has commanded it off. HZ-ICE detects this condition by monitoring current in a zone that should be off: if current is flowing when the panel has not commanded that zone to heat, a welded contactor alarm is generated. This is a safety-critical fault — the affected zone should be disabled from the dashboard and service called immediately.

How does HZ-ICE detect a broken heating cable?

Each of HZ-ICE’s circuits is monitored by a dedicated current transformer. When the panel activates a circuit, it measures the current the circuit is drawing. If the circuit draws no current when it should be heating, the panel logs a load fault alarm — indicating the heating cable is broken, the breaker has tripped, or the circuit has otherwise failed. The alarm appears on the dashboard and is reported to the building automation system via BACnet. This detection happens automatically, without any manual inspection of the heating cable or driveway surface.

Is HZ-ICE connected to the internet?

No. HZ-ICE is not connected to the internet. The panel’s Wi-Fi is a local access point — it only reaches approximately 30 feet from the panel and exists only for the local dashboard. No cloud service, no remote update capability, and no external access is possible without a building-side VPN or similar arrangement set up by the building’s IT team. Heatizon has no remote access to any HZ-ICE panel.

Can HZ-ICE integrate with a building automation system?

Yes. HZ-ICE exposes 35 BACnet/IP objects to the building automation system — compatible with any BACnet-capable BAS platform including Niagara, Metasys, and similar systems. No additional drivers or licensing are required. The BACnet controller (BACnet/IP certified) is battery-backed — it continues reporting to the BAS for approximately 7 hours after grid AC fails, so the building automation system receives outage notification before anyone else knows the panel is on battery. If the building does not have a BAS, the local Wi-Fi dashboard provides full visibility and control without any BACnet configuration.

How does the HZ-ICE local dashboard work?

Every HZ-ICE panel includes a built-in web dashboard hosted on the panel’s own Wi-Fi access point. No app installation, no account creation, and no connection to the building’s network is required. To access the dashboard, connect a phone, tablet, or laptop to the panel’s Wi-Fi network (the network name and password are on a label inside the panel door) and open any web browser. The dashboard shows real-time zone current draw, runtime hours, outdoor temperature, snow sensor status, battery health, and any active alarms — and allows adjustment of temperature cutoffs, zone enables, and manual override duration.

What makes HZ-ICE different from a standard radiant heating contactor panel?

A standard contactor panel turns heating circuits on and off — and that is all it does. HZ-ICE monitors what is actually happening in each zone. Per-zone current sensing detects a broken heating cable the moment it fails — not when someone notices the driveway is still covered in snow in February. BACnet/IP integration exposes all panel signals to the building automation system. A local Wi-Fi dashboard lets anyone with a phone check panel health without opening the enclosure or calling a technician. Battery backup keeps alarm reporting running for approximately 7 hours after grid power fails.

How many zones does HZ-ICE control?

HZ-ICE controls up to 6/12 independent heating circuits — each circuit is independantly switched by a project-specific voltage/amperage GFEP definite-purpose contactor and monitored by a dedicated current transformer. Each zone can be independently monitored and controlled. For installations requiring more than 12 zones, Heatizon will be offering larger circuit panels in the same smart platform family.

What is the HZ-ICE smart snow melt control panel?

HZ-ICE is Heatizon’s smart multi-zone snow melt control panel for high-end residential and commercial installations. Unlike a standard relay panel, HZ-ICE monitors every zone individually — detecting broken heating cables, stuck contactors, and load faults in real time. Every panel includes a built-in local Wi-Fi web dashboard, BACnet/IP integration for building automation systems, and battery backup that keeps alarms reporting through grid power outages. HZ-ICE is engineered to drive Heatizon’s Hott-Wire, Cozy Heat, and GutterMelt heating cables across driveways, walkways, roof valleys, gutters, and pedestal paver systems.

What is included with a Heatizon custom panel?

Every Heatizon custom panel includes complete wiring diagrams and full end-user support. The panel is engineered to the project specifications, assembled in Heatizon’s UL 508A certified facility, and shipped ready for installation. Project-specific indicators, switches, and controllers are integrated as required.