Gutter Melt SR 120, 208, 240, and 277V Self Regulating roof and gutter heat trace cables are designed to economically and effectively provide heat to maintain water flow paths on eaves, in gutters, downspouts and drains. GutterMelt SR cables produce wattages of 5, 9, 12 and up to 24 watts per foot at 32° F in snow and ice These cables provide reliable freeze protection while carrying an industry leading 10 year warranty. GutterMelt is a great choice for either residential, commercial or industrial projects. Our Self Regulating technology is effectively used to heat trace pipes to keep fluids flowing.
Features:
Cable Specifications:
| Bus Wire..... |
16 AWG, Nickel Plated Copper Heating |
| Core..... |
Radiation Cross-Linked Polyolefin |
| Primary Dialectric Insulation..... |
Radiation Cross-Linked Polyolefin |
| Metallic Braid..... |
Tinned Copper Braid |
| Outer Jacket..... |
Polyolefin |
| Minimum Bending Radius..... |
1" |
| Supply Voltage..... |
120 or 208-277 VAC up to 480VAC |
| Max. Maintenance Temp..... |
150° F (65°C) |
| Max Intermittent Exposure Temp..... |
212° F (100°C) |
| Nominal Power Output at 32° F..... |
5, 9, 12 up to 24 watts/ft |
GutterMelt Applications : Keep the water flowing to the ground with Heatizon Gutter Melt. Gutter Melt comes in several outputs to meet residential and industrial applications. Two runs of cable are recommended for common applications in gutters and downspouts.
- Roof Eaves
- Roof Valleys
- Gutters
- Downspouts
- Pipe Tracing
- Industrial Applications
|
 |
|
Technical Tables and Calculator :
Required GutterMelt |
Roof Overhang |
B |
A |
Spacing Factor |
Heating Width |
Heating Height |
12" |
2ft |
18" |
2 |
24" |
2ft |
30" |
3 |
36" |
2ft |
42" |
4 |
The calculation is based on two runs of GutterMelt in Gutters and Downspouts. Fields not requiring heat enter 0.
GutterMelt Length/Feet Calculator
|
GutterMelt Output Curve  |
Maximum Allowable Circuit Lengths per Breaker Rating for GutterMelt |
| |
GutterMelt 5 W/ft |
120V |
240V |
Breaker Size
Startup@40°F
Startup@0°F
Startup@-20°F |
15A
300 ft
200 ft
180 ft |
20A
--
270 ft
230 ft |
30A
--
330 ft
330 ft |
40A
--
--
-- |
15A
660 ft
410 ft
360 ft |
20A
--
560 ft
480 ft |
30A
--
660 ft
660 ft |
40A
--
--
-- |
| |
GutterMelt 9 W/ft |
120V |
240V |
Breaker Size
Startup@40°F
Startup@0°F
Startup@-20°F |
15A
150 ft
95 ft
85 ft |
20A
200 ft
125 ft
100 ft |
30A
210 ft
190 ft
170 ft |
30A
210 ft
190 ft
170 ft |
15A
295 ft
195 ft
170 ft |
20A
390 ft
250 ft
225 ft |
30A
420ft
375 ft
340 ft |
40A
--
420 ft
420 ft |
| |
GutterMelt 12 W/ft |
120V |
240V |
Breaker Size
Startup@40°F
Startup@0°F
Startup@-20°F |
15A
115 ft
70 ft
60 ft |
20A
150 ft
95 ft
85 ft |
30A
180 ft
145 ft
120 ft |
40A
--
180 ft
165 ft |
15A
230 ft
150 ft
130 ft |
20A
305 ft
200 ft
175 ft |
30A
360 ft
300 ft
260 ft |
40A
--
360 ft